Maintenance Requirements
  • The level transmitter requires no special maintenance.
Basic Configuration
  1. Initial Setup:
    • Press the E (Enter) key to access the primary menu.
    • Select "Basic Setup" and press E.
  2. Tank Geometry:
    • In the secondary menu, choose the tank shape (e.g., "Flat Ceiling" for flat-top tanks).
    • Press E to confirm.
  3. Medium Type:
    • In the tertiary menu, select the medium type (e.g., "Liquid").
    • Press E.
  4. Surface Condition:
    • In the quaternary menu, select the surface state (e.g., "Turb Surface" for turbulent liquid surfaces).
    • Press E.
  5. Empty Calibration:
    • Set the "Empty Calibr." distance (e.g., 5.500 m - distance from flange to tank bottom).
      • Press or to adjust the value.
    • Press E to confirm.
  6. Blind Zone (Blocking Distance):
    • Set "Blocking Dist" (e.g., 0.35 m) to define the non-measurement zone near the sensor.
    • Press E.
  7. Full Calibration:
    • Set the "Full Calibr." span (e.g., 5.15 m = 5.500 m - 0.35 m).
      • Press or to adjust.
    • Press E repeatedly to return to the primary menu.
    • Press ↓ + ↑ simultaneously to exit to the display screen.
Display Unit Configuration
  1. Access Menu:
    • Press E to enter the primary menu.
    • Navigate to "Linearisation" using or , then press E.
  2. Unit Selection:
    • In the secondary menu, select "Level DU" and choose meters (m) as the unit.
    Note:
    • "Ullage CU" displays the level as a percentage (e.g., 50% = half-full).