Product Details:
Contact Now
Chat Now
|
Output Signal: | 4 To 20 MA DC With Digital Communication (HART 5/HART 7 Protocol) | Measurement Span (capsule): | 0.5 To 5 KPa (2.0 To 20 InH2O) (For Wetted Parts Material Code S) |
---|---|---|---|
Process Connections: | Without Process Connector (1/4 NPT Female On The Cover Flanges) | Bolts And Nuts Material: | B7 Carbon Steel |
Installation: | Horizontal Piping And Left Side High Pressure | Amplifier Housing: | Cast Aluminum Alloy |
Electrical Connection: | 1/2 NPT Female, Two Electrical Connections And A Blind Plug | Mounting Bracket: | 304 SST 2-inch Pipe Mounting, Flat Type (for Horizontal Piping) |
Highlight: | eja110e yokogawa pressure transmitter,eja110e yokogawa differential pressure transmitter,20ma yokogawa pressure transmitter |
Attribute | Value |
---|---|
Output signal | 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol) |
Measurement span (capsule) | 0.5 to 5 kPa (2.0 to 20 inH2O) (For Wetted parts material code S) |
Process connections | without process connector (1/4 NPT female on the cover flanges) |
Bolts and nuts material | B7 carbon steel |
Installation | Horizontal piping and left side high pressure |
Amplifier housing | Cast aluminum alloy |
Electrical connection | 1/2 NPT female, two electrical connections and a blind plug |
Mounting bracket | 304 SST 2-inch pipe mounting, flat type (for horizontal piping) |
EJA-E series ensures specification conformance to at least ±3σ.
(includes terminal-based linearity, hysteresis, and repeatability)
Parameter | Value |
---|---|
Reference accuracy | X ≤ span | ±0.055% of Span X > span | ±(0.005+0.02 URL/span)% of Span |
X | 2 kPa (8 inH2O) |
URL (upper range limit) | 5 kPa (20 inH2O) |
Parameter | Value |
---|---|
Reference accuracy | X ≤ span | ±0.055% of Span X > span | ±(0.005+0.0025 URL/span)% of Span |
X | 5 kPa (20 inH2O) |
URL (upper range limit) | 100 kPa (400 inH2O) |
Parameter | Value |
---|---|
Reference accuracy | X ≤ span | ±0.055% of Span X > span | ±(0.005+0.01 URL/span)% of Span |
X | 100 kPa (400 inH2O) |
URL (upper range limit) | 500 kPa (2000 inH2O) |
Parameter | Value |
---|---|
Reference accuracy | X ≤ span | ±0.055% of Span X > span | ±(0.005+0.005 URL/span)% of Span |
X | 1.4 MPa (200 psi) |
URL (upper range limit) | 14 MPa (2000 psi) |
Measurement Types | |
---|---|
Primary Variable | Differential Pressure (DP) |
Secondary Variable | Static Pressure (SP) |
Reference Accuracy | |
Primary Variable | ±0.055% of Span |
Secondary Variable | ±0.5% of Span available |
Response Time | |
Primary Variable | 90 msec |
Secondary Variable | 360 msec |
Long Term Stability | |
Primary Variable | ±0.1% of URL per 10 years |
Over-pressure Effect | |
Primary Variable | ±0.03% of URL |
Rangeability | |
Primary Variable | 100:1 |
Contact Person: Ms. Joy chen
Tel: +8615012673027
Fax: 86--15012673027