उत्पाद विवरण:
संपर्क करें
अभी चैट करें
|
| रिसाव वर्तमान: | <3 μA -20...85 डिग्री सेल्सियस (-4...185 डिग्री फारेनहाइट) पर | लेबलिंग: | सामने लेबलिंग के लिए जगह |
|---|---|---|---|
| सुरक्षा अखंडता स्तर: | एसआईएल 3 | सुरक्षा की डिग्री: | आईईसी 60529:2001 |
| Supply Connection: | via 14-channel flat cable form master KFD2-HMM-16 | आउटपुट प्रतिरोध: | 100 Ω या छोटा, कैपेसिटिव कपलिंग |
| परिवेश का तापमान: | -20 ... 65 डिग्री सेल्सियस (-4 ... 149 डिग्री फारेनहाइट) | Dimensions: | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D) , housing type B1 |
| प्रमुखता देना: | SIL 3 P+F Sensors,SIL 3 P+F hart multiplexer,p&f hart multiplexer KFD0-HMS-16 |
||
| Attribute | Value |
|---|---|
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) |
| Labeling | Space for labeling at the front |
| Safety Integrity Level (SIL) | SIL 3 |
| Degree of protection | IEC 60529:2001 |
| Supply Connection | Via 14-channel flat cable form master KFD2-HMM-16 |
| Output resistance | 100 Ω or smaller, capacitive coupling |
| Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) |
| Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D), housing type B1 |
| Safety Integrity Level (SIL) | SIL 3 |
| Connection | Via 14-channel flat cable form master KFD2-HMM-16 |
| Conformity | HART field device input (revision 5 to 7) |
| Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) |
| Terminating resistor | External 230 ... 500 Ω standard (up to 1000 Ω possible) |
| Output voltage | ≥ 400 mV ss (with the terminator resistance specified above) |
| Output resistance | 100 Ω or smaller, capacitive coupling |
| Input impedance | According to HART specification |
| Input voltage range | 0.08 ... 4 V ss; typ. ± 5.2 V as local reference |
| Labeling | Space for labeling at the front |
| Electromagnetic compatibility | Directive 2014/30/EU EN 61326-1:2013 (industrial locations) |
| Degree of protection | IEC 60529:2001 |
| Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) |
| Degree of protection | IP20 |
| Mass | Approx. 100 g |
| Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D), housing type B1 |
| Mounting | On 35 mm DIN mounting rail according to EN 60715:2001 |
| Certificate | PF 07 CERT 1143 X |
| Marking | |
| Directive conformity | Directive 2014/34/EU EN 60079-0:2012+A11:2013 EN 60079-15:2010 |
व्यक्ति से संपर्क करें: Ms. Joy chen
दूरभाष: +8615012673027
फैक्स: 86--15012673027