होम उत्पादएमटीएल सुरक्षा बाधा

MTL4514D MTL5514D Hazardous Area Switch Proximity Detector Interface

मैं अब ऑनलाइन चैट कर रहा हूँ

MTL4514D MTL5514D Hazardous Area Switch Proximity Detector Interface

MTL4514D MTL5514D Hazardous Area Switch Proximity Detector Interface
MTL4514D MTL5514D Hazardous Area Switch Proximity Detector Interface MTL4514D MTL5514D Hazardous Area Switch Proximity Detector Interface MTL4514D MTL5514D Hazardous Area Switch Proximity Detector Interface

बड़ी छवि :  MTL4514D MTL5514D Hazardous Area Switch Proximity Detector Interface

उत्पाद विवरण:
उत्पत्ति के प्लेस: इंगलैंड
ब्रांड नाम: MTL
प्रमाणन: CE
मॉडल संख्या: एमटीएल4514
भुगतान & नौवहन नियमों:
न्यूनतम आदेश मात्रा: 1पीसी
मूल्य: बातचीत योग्य
पैकेजिंग विवरण: मानक कार्टन पैकिंग
प्रसव के समय: अनुरोध पर
भुगतान शर्तें: टी/टी
आपूर्ति की क्षमता: प्रति माह 100pcs
संपर्क करें अभी चैट करें

MTL4514D MTL5514D Hazardous Area Switch Proximity Detector Interface

वर्णन
चैनलों की संख्या: एक स्विच का स्थान: ज़ोन 0, IIC, T6 खतरनाक क्षेत्र Div.1, समूह ए, खतरनाक स्थान
निकटता डिटेक्टर का स्थान: जोन 0, आईआईसी, टी4-6 खतरनाक क्षेत्र, यदि उपयुक्त रूप से प्रमाणित हो Div.1, समूह ए, खतरनाक स्थान खतरनाक-क्षेत्र इनपुट: BS EN60947–5–6 के अनुरूप इनपुट: 2001 निकटता डिटेक्टरों के लिए मानक (NAMUR)
सेंसर पर लगाया गया वोल्टेज: 1kΩ ±10% से 7 से 9V डीसी सुरक्षित क्षेत्र का आउटपुट: सामान्य रूप से खुले संपर्क के साथ दो, एकल पोल रिले
प्रमुखता देना:

MTL5514D Switch/Proximity Detector Interface

,

MTL4514D Switch/Proximity Detector Interface

,

Harsh Environments Switch/Proximity Detector Interface

MTL4514D – MTL5514D Switch/Proximity Detector Interface for Harsh Environments
Product Specifications
Attribute Value
Number of channels One
Location of switch Zone 0, IIC, T6 hazardous area Div.1, Group A, hazardous location
Location of proximity detector Zone 0, IIC, T4–6 hazardous area, if suitably certified Div.1, Group A, hazardous location
Hazardous–area inputs Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Voltage applied to sensor 7 to 9V dc from 1kΩ ±10%
Safe-area output Two, single pole relays with normally-open contact
Product Description

The MTLx514D enables two safe-area loads to be controlled, through relays, by a proximity detector or switch located in a hazardous area. When selected, open or short circuit conditions in the field wiring are detected by the line fault detect (LFD) facility and indicated on the top of the module. Switches are provided to select phase reversal and to enable the line fault detection.

Relay Characteristics
Specification MTL4514D MTL5514D
Response time 10ms maximum 10ms maximum
Contact rating (Safe Area) 10W, 0.5A, 35V dc 250V ac, 2A, cosØ >0.7, 40V dc, 2A, resistive load
Contact rating (Zone 2) 10W, 0.5A, 35V dc 35V, 2A, 100VA