Product Details:
Contact Now
Chat Now
|
Number Of Protected Signal Lines: | 2 | Topology: | Grounded |
---|---|---|---|
Safety Integrity Level (SIL): | SIL 3 | Connection: | Protected Area: Terminals 7, 8 Unprotected Area: Terminals 1, 2 |
Rated Current: | 250 MA | Leakage Current: | < 10 µA At 24 V And 25 °C (77 °F) , Line-line |
Nominal Voltage: | 24 V DC | Maximum Continuous Operating Voltage: | 30 V DC |
Highlight: | P+F Surge Protection Barrier,Surge Protection Barrier K-LB-1.30G,8 Terminals P+F Sensors |
Attribute | Value |
---|---|
Number of protected signal lines | 2 |
Topology | Grounded |
Safety Integrity Level (SIL) | SIL 3 |
Connection | Protected area: terminals 7, 8 Unprotected area: terminals 1, 2 |
Rated current | 250 mA |
Leakage current | < 10 µA at 24 V and 25 °C (77 °F), line-line |
Nominal voltage | 24 V DC |
Maximum continuous operating voltage | 30 V DC |
Series resistance | < 0.5 Ω per line |
Impulse rating | 10 kV/5 kA (category C2) 2 kV/2 kA (category D1) |
Impulse discharge current (10/350 µs) | 2 kA per line (2x) |
Nominal discharge current (8/20 µs) | 5 kA per line (10x) |
Rated surge current (8/20 µs) | 10 kA per line (1x) |
Total discharge current (8/20 µs) | 20 kA (1x) |
Voltage protection level | max. 100 V line-line for nominal discharge current In max. 50 V line-earth for nominal discharge current In |
Impulse reset time | < 30 ms |
Degree of protection | IP20 |
Connection | Screw terminals |
Core cross section | 2 x 2.5 mm² |
Mass | Approx. 100 g |
Dimensions (W x H x D) | 12.5 x 115 x 116 mm (0.5 x 4.5 x 4.6 inch) |
Mounting | On 35 mm DIN mounting rail according to EN 60715:2001 |
EU-type examination certificate | PTB 00 ATEX 2176 X |
Marking | II 2(1)G Ex ia IIC T6/T5/T4 |
Temperature class | T6 for ambient temperature ≤ 50 °C T5 for ambient temperature ≤ 70 °C T4 for ambient temperature ≤ 80 °C |
Voltage | 30 V |
Current | 250 mA |
Contact Person: Ms. Joy chen
Tel: +8615012673027
Fax: 86--15012673027